408 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
Table 343 - Under kVA Trip Delay (Parameter 403)
Under kVA Trip Level
Under kVA Trip Level (Parameter 404) allows you to define the apparent power
(kVA) at which the E300 relay trips on an under apparent power (kVA). It is user-
adjustable from 0…2,000,000 kVA.
Table 344 - Under kVA Trip Level (Parameter 404)
Under kVA Warning
The E300 relay indicates an Under kVA warning if:
No warning currently exists
Under kVA Warning is enabled
Current is present
Voltage is present
Under kVA Inhibit Time has expired
The total apparent power (kVA) is equal to or less than the Under kVA
Wa
rn
in g L e vel
When the Under kVA Warning conditions are satisfied, the:
TRIP/WARN LED flashes a yellow 2-long / 7-short blink pattern
Bit 6 in Power Warning Status (Parameter 12) sets to 1
Default Value 1.0
Minimum Value 0.1
Maximum Value 25.0
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 10
Units Seconds
Default Value 0.000
Minimum Value 0.000
Maximum Value 2,000,000.000
Parameter Type DINT
Size (Bytes) 4
Scaling Factor 1000
Units kVA
IMPORTANT
The Under kVA Inhibit Time starts after a phase voltage transitions from 0V to
20V L-L and a phase of load current transitions from 0 A to 30% of the
minimum FLA setting of the device. The E300 relay does not begin monitoring
for an under apparent power (kVA) condition until the Under kVA Inhibit Time
expires.