Rockwell Automation Publication 193-UM015E-EN-P - October 2015 667
Parameter List Appendix B
Analog4 Setup
(continued)
554 InAMod4C2TripDly C.Analog4.Ch02InputTripDelay Analog Module 4
Input Channel 02
Trip Delay
USINT 1 10 0 250 10
Seconds
555 InAMod4C2TripLvl C.Analog4.Ch02InputTripLimit Level (in selected
Units) where
Analog Input
generates a trip
UINT 2 1 -32768 32767 0
556 InAMod4C2WarnLvl C.Analog4.Ch02InputWarnLimit Level (in selected
Units) where
Analog Input
generates a
warning
UINT 2 1 -32768 32767 0
557 OutAnMod4Type C.Analog4.Ch00OutputRangeType_0
C.Analog4.Ch00OutputRangeType_1
C.Analog4.Ch00OutputRangeType_2
C.Analog4.Ch00OutputRangeType_3
Assignment for
Analog Module 4
Output function
USINT 1 1 0= Disabled
1= 4To20mA
2= 0To20mA
3= 0To10Volts
4= 1To5Volts
5= 0To5Volts
0
558 OutAnMod4Select C.Analog4.Ch00OutputMode Assignment of
parameter data
value to drive
Analog Module 4
Output
USINT 1 1 0= AveragePctFLA
1= ScaledAvgPctFLA
2= PercentTCU
3= GFCurrent
4= CurrentUnbalance
5= AvgLLVoltage
6=VoltLLUnbalance
7= TotalkW
8= TotalkVA
9= TotalkVAR
10= TotalPF
11= UserDLXData
0
559 OutAnMod4EFltAct C.Analog4.Ch00OutputFaultMode_0
C.Analog4.Ch00OutputFaultMode_1
Analog Module 4
Output action on
an Expansion Bus
fault
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
560 OutAnMod4PFltAct C.Analog4.Ch00OutputProtectionFaultMode_0
C.Analog4.Ch00OutputProtectionFaultMode_1
Analog Module 4
Output action on a
protection fault
USINT 1 1 0= Zero
1= Maximum
2= Minimum
3= HoldLastState
0
Output Setup
561 FnlFltValStDur C.FaultValueStateDuration
Final Fault Value
State Duration
SINT 1 1 0 = Forever 127 0 Sec
562 OutPt00FnlFltVal C.Pt00OutputFaultFinalState
Output Relay 0
Final Fault Value
BOOL 1 1
0 = Open
1 = Close
0
563 OutPt01FnlFltVal C.Pt01OutputFaultFinalState
Output Relay 1
Final Fault Value
BOOL 1 1
0 = Open
1 = Close
0
564 OutPt02FnlFltVal C.Pt02OutputFaultFinalState
Output Relay 2
Final Fault Value
BOOL 1 1
0 = Open
1 = Close
0
565 OutDig1FnlFltVal C.Digital1FaultFinalState
Digital Module 1
Output Relay Final
Fault Value
BOOL 1 1
0 = Open
1 = Close
0
566 OutDig2FnlFltVal C.Digital2FaultFinalState
Digital Module 2
Output Relay Final
Fault Value
BOOL 1 1
0 = Open
1 = Close
0
567 OutDig3FnlFltVal C.Digital3FaultFinalState
Digital Module 3
Output Relay Final
Fault Value
BOOL 1 1
0 = Open
1 = Close
0
568 OutDig4FnlFltVal C.Digital4FaultFinalState
Digital Module 4
Output Relay Final
Fault Value
BOOL 1 1
0 = Open
1 = Closed
0
569 NetStrtComFltAct C.LogicDefinedDataFaultMode
Network Start
Comm Fault Action
BOOL 1 1
0 = GoToNetStCFltVal
1 = HoldLastState
0
570 NetStrtComFltVal C.LogicDefinedDataFaultValue
Network Start
Comm Fault Value
BOOL 1 1
0 = Open
1 = Close
0
571 NetStrtComIdlAct C.LogicDefinedDataProgMode
Network Start
Comm Idle Action
BOOL 1 1
0 = GoToNetStCIdlVal
1 = HoldLastState
0
572 NetStrtComIdlVal C.LogicDefinedDataProgValue
Network Start
Comm Idle Value
BOOL 1 1
0 = Open
1 = Close
0
573 NetStrtFnlFltVal C.LogicDefinedDataFaultFinalState
Network Start
Final Comm Fault
Value
BOOL 1 1
0 = Open
1 = Close
0
Voltage Setup 574 VoltageScale C.VoltageScale
Voltage value scale
factor
BOOL 1 1
0 = Volts
1 = kVolts
0
Group
Param
No.
Parameter Name Device Profile Tag Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units