EasyManua.ls Logo

AutomationDirect DL205 - Module Resolution 16-Bit (Unipolar Voltage Input); Module Resolution 15-Bit Plus Sign(Bipolar Voltage Input)

Default Icon
359 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DL205 Analog Manual, 7th Edition Rev. D
7-21
Chapter 7: F2-04THM, 4-Channel Thermocouple Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B
C
D
Module Resolution 16-Bit (Unipolar Voltage Input)
Unipolar analog signals are converted into
65536 counts ranging from 0–65535 (2
16
).
For example, with a 0–156mV signal range,
78mV would be 32767. A value of 65535
represents the upper limit of the range.
H or L = high or low limit of the range
Module Resolution 15-Bit Plus
Sign(Bipolar Voltage Input)
The module has 16-bit unipolar or 15-bit
+ sign bipolar resolution. Bipolar analog
signals are converted into 32768 counts
ranging from 0–32767 (2
15
). For example,
with a -156mV–156mV signal range,
156mV would be 32767. The bipolar
ranges utilize a sign bit to provide 16-bit
resolution. A value of 32767 can represent
the upper limit of either side of the range.
Use the sign bit to determine negative
values.
H or L = high or low limit of the range
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
b
C
D
5
3556032767
0V
78 mV
156mV
0V
2.5V
5V
Counts
Unipolar Resolution =
H – L
65535
3276
73
27670
-- 5V
0V
5V
-- 156mV
0V
156mV
Counts
Bipolar Resolution =
H – L
32767