DL205 Analog Manual, 7th Edition Rev. D
12-2
Chapter 12: F2-02DAS-1, 4-20mA Isolated 2-Channel Analog Current Output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Module Specifications
The F2-02DAS-1 Analog Output module provide several
hardware features:
Analog outputs are isolated from channel to channel
and channel to PLC logic.
The module has a removable terminal block so the
module can be easily removed or changed without
disconnecting the wiring.
All channels can be updated in one scan if either a DL240,
a DL250-1 or a DL260 CPU is used in the PLC.
Outputs are sourced through external loop supply.
Loop power supply requirements:
18–32 VDC
Firmware Requirements:
To use this module, DL230 CPUs must have firmware
version 1.7 or later.
To use the pointer method for writing values, DL240 CPUs
require firmware version 2.9 or later.
DL250 CPUs require firmware version 1.30 or later.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
+V1
+I1
N/C
+V2
+I2
0V1
–I1
NC
0V2
–I2
F2-02DAS-1
OUTANALOG
2CH
F2-02DAS-1
12-32VDC
ANALOG OUT
4-20mA
+V
1
+I
1
N
/C
+V
2
+I
2
0
V
1
I
1
N
C
0
V
2
I2
F
2-02DA
S
-1
O
UT
F
2-02DA
S
-
1
1
2-
3
2VD
C
A
NAL
OG
OUT
4-
20
m
A
A
NAL
OG
A
2C
H
F2-02DAS-1

Table of Contents

Other manuals for AutomationDirect DL205

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect DL205 and is the answer not in the manual?

AutomationDirect DL205 Specifications

General IconGeneral
BrandAutomationDirect
ModelDL205
CategoryController
LanguageEnglish

Related product manuals