Page #311 background image
DL205 Analog Manual, 7th Edition Rev. D
15-19
Chapter 15: F2-8AD4DA-1 8-Ch. In / 4-Ch. Out Analog Current Combination
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B
C
D
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
b
C
D
Module Configuration Example 3:
Number of Channels = 4 in, 2 out,
Data Format = BCD in, BCD out,
Input Resolution = 12 bit,
Input Track and Hold = all inputs minimum value.
NOTE: Binary data format is recommended for 14 or 16 bit resolution input data, especially if the input data is to
be used in any math instructions (DL205 User Manual, ch.5). There is only one V-memory word (16 bits) available for the
actual data. Although the 12 bit resolution maximum value of 4095 can be stored in one word using either binary or BCD
formats, the 14 and 16 bit resolution maximum values of 16383 and 65535 both exceed the BCD format’s maximum single
word capacity of 9999. Double word math would be required for 14 or 16 bit data in BCD format. Binary data format is
also useful for displaying data on some operator interfaces.
SP0
LD
K
LDA
O2000
OUT
V7673
Loads aconstantthatspecifies the numberofchannelstoscan and
thedataformat. (See note below regarding dataformat. )(Theleading
zero in this LD instructionisshownfor clarity. It canbe entered by the
programmer, but it will be droppedbythe programming software.)
Theupper byte appliestothe inputs. Themostsignificant nibble
(MSN)selects the dataformat(0=BCD, 8=Binary), and theLSN
selects the number of channels(1, 2, 3, 4, 5, 6, 7, or 8) to scan.
Thelower byte appliestothe outputs. Themostsignificant nibble
(MSN)selects the dataformat(0=BCD, 8=Binary), and theLSN
selects the number of channels(1, 2, 3, or 4) to scan.
This constant designatesthe firstV-memorylocationthatwillbe
used to storethe inputdata.For example, theO2000 entered here
would mean: Ch1--V2000, V2001;Ch2 -- V2002, V2003; Ch3--
V2004,V2005; Ch4--V2006,V2007.For eachchannel,the 1stword
holds thedata, and the 2nd word is needed only when displaying 14
or 16 bit datainBCD format.The 2ndwordcontains themost
significant digitinthose cases.
Theconstant O2000isstored here. V7673isassigned to slot 3 and
acts as a pointer,whichmeansthe CPUwilluse thevalue in this
locationtodetermine exactlywheretostore theincomingdata.
OUT
V7663
Special V-memory location assignedtoslot3that contains the
numberofinput and output channels.
LDA
O2020
OUT
V7703
This constant designates thefirst V-memory locationthatwillbe
used forthe analog outputdata. Forexample,the O2020 entered
herewould mean:Ch1 -- V2020, V2021;Ch2 -- V2022,V2023. For
eachchannel,the 1stwordholds thedata, and the 2nd word is
needed only when displaying 14 or 16 bit datainBCD format.The
2nd word contains themos tsignificant digitinthosecases.
Theconstant O2020isstored here. V7703isassigned to slot 3 and
acts as a pointer,whichmeansthe CPUwilluse thevalue in this
location to determine exactlywhereto obtain the outputdata.
0402
LD
K0
Loads aconstantthatspecifies theresolutions for eachofthe input
channels. This constant is determinedbythe values of two bitsper
channel,asshown previously in “InputResolutions Selection Bits”.
Theconstant 0configures eachofthe eightinput channelsfor 12
bits.
OUT
V36403
SpecialV-- memory location assigned to slot 3that containsthe
resolution settings foreachofthe inputchannels.
LD
K5555
Loadsaconstant that specifiesthe track and hold settingsfor each
of theinputchannels. This constant is determinedbythe values of
twobits per channel,aspreviously shownin“Track and Hold
Selection Bits”. Theconstant 5555(hex)configures eachofthe eight
inputchannelstotrack and hold theminimum value.
OUT
V36423
SpecialV-- memory location assigned to slot 3that containsthe track
and holdsettingsfor eachofthe inputchannels..

Table of Contents

Other manuals for AutomationDirect DL205

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect DL205 and is the answer not in the manual?

AutomationDirect DL205 Specifications

General IconGeneral
BrandAutomationDirect
ModelDL205
CategoryController
LanguageEnglish

Related product manuals