DL205 Analog Manual, 7th Edition Rev. D
3-14
Chapter 3: F2-04AD-2 , F2-04AD-2L, 4-Channel Analog Voltage Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Module Resolution
Since the module has 12-bit unipolar resolution, the
analog signal is converted into 4096 counts ranging
from 0 - 4095 (2
12
). For example, with a 0–10V
scale, a 0V signal would be 0 and a 10V signal would
be 4095. This is equivalent to a a binary value of
0000 0000 0000 to 1111 1111 1111, or 000 to FFF
hexadecimal. The diagram shows how this relates to
the signal range.
Each count can also be expressed in terms of the
signal level by using the equation shown.
Each count can also be expressed in terms of the signal level by using the equation shown.
The following table shows the smallest detectable signal change that will result in one LSB
change in the data value for each input signal range.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
+V
0V
0 4095
Unipolar
Ranges
Unipolar Resolution
=
H–L
4095
HorL=highorlow limit of therange
+V
0V
0 4095-- 4095
-- V
Bipolar
Ranges
Bipolar Resolution
=
H–L
8191
Voltage Range
Signal Span
(H – L)
Divide By
Smallest Detectable
Change
0 – +10V
10 V 4095 2.44 mV
- 10 – +10V
20 V 8191 2.44 mV
0 – + 5V
5 V 4095 1.22 mV
- 5V – + 5V
10 V 8191 1.22 mV

Table of Contents

Other manuals for AutomationDirect DL205

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect DL205 and is the answer not in the manual?

AutomationDirect DL205 Specifications

General IconGeneral
BrandAutomationDirect
ModelDL205
CategoryController
LanguageEnglish

Related product manuals