The following tables provide the specifications for the F2–02DA –2 and F2-02DA-2L Analog
Output Modules.
NOTE: One count in the specifications table is equal to one least significant bit of the analog data value (1 in 4096)
Output Specifications
Number of Channels
2
Output Range
0–5V, 0–10V, ±5V, ±10V
Resolution
12 bit (1 in 4096)
Output Type
Single ended, 1 common
Peak Output Voltage
15VDC (clamped by transient voltage suppressor)
Load Impedance
2000q minimum
Load Capacitance
0.01 µF maximum
Linearity Error (end to end)
±1 count (±0.025% of full scale) maximum
Conversion Settling Time
5 µs maximum (full scale change)
Full-scale Calibration Error
(offset error included)
±12 counts maximum, @ 25°C (77°F) unipolar
±16 counts maximum, @ 25°C (77°F) bipolar
Offset Calibration Error
±3 counts maximum, @ 25°C (77°F) unipolar
±8 counts maximum, @ 25°C (77°F) bipolar
Maximum Inaccuracy
Unipolar ranges ± 0.3% @ 25°C (77°F)
± 0.45% 0–60°C (32–140°F)
Bipolar ranges ± 0.4% @ 25°C (77°F)
± 0.55% 0–60°C (32–140°F)
Accuracy vs. Temperature
±50ppm/°C full scale calibration change
(including maximum offset change of 2 counts)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
General Specifications
PLC Update Rate
1 channel per scan maximum (D2-230 CPU)
2 channels per scan maximum (D2-240/250-1/260 CPUs)
Digital Outputs
Output Points Required
12 binary data bits, 2 channel ID bits, 1 sign bit
16 point (Y) output module
Power Budget Requirement
40mA @ 5VDC (supplied by the base)
External Power Supply
F2-02DA-2: 24VDC, 60mA (outputs fully loaded)
F2-02DA-2L: 12VDC, 70mA (outputs fully loaded)
Operating Temperature
0–60°C (32–140°F)
Storage Temperature
–20–70°C (-4–158°F)
Relative Humidity
5–95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304