EasyManuals Logo

AutomationDirect DL205 Manual

Default Icon
359 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #237 background imageLoading...
Page #237 background image
DL205 Analog Manual, 7th Edition Rev. D
12-3
Chapter 12: F2-02DAS-1, 4-20mA 2-Channel Analog Current Output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
The following tables provide the specifications for the F2–02DAS –1, Isolated Analog Output
Module.
NOTE: One count in the specifications table is equal to one least significant bit of the analog data value (1 in 65536)
Analog Output Configuration Requirements
The F2-02DAS-1 Analog output appears as a 32 discrete output points. The module can be
installed in any slot of a DL205 system, but the available power budget and discrete I/O points
are the limiting factors. Check the DL205 PLC User Manual for the particular model of CPU
and I/O base being used for information regarding power budget and number of local, local
expansion or remote I/O points.
Output Specifications
Number of Channels
2, isolated (2 commons)
Output Range
4–20 mA
Resolution
16 bit (1 in 65536)
Output Type
Current sourcing
Isolation Voltage
±750V continuous, channel to channel, channel to logic
Loop Supply
18–32 VDC
Max Load Impedance
525q
Linearity Error (end to end)
±10 counts (±0.015% of full scale) maximum
Conversion Settling Time
3ms to 0.1% of full scale
Gain Calibration Error
±32 counts (±0.05%)
Offset Calibration Error
±13 counts (±0.02%)
Output Drift
50ppm / ° C
Maximum Inaccuracy
±0.07% @ 25° C (77° F)
±0.18% 0–60° C (32–140° F)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
General Specifications
PLC Update Rate
1 channel per scan maximum (multiplexing)
2 channels per scan maximum (pointer –
DL240/DL250-1/DL260 only)
Digital Outputs /
Output Points Required
16 binary data bits, 2 channel ID bits;
32 point (Y) output module
Power Budget Requirement
100mA @ 5VDC (supplied by the base)
External Power Supply
18–24 VDC 50mA per channel, Class 2
Operating Temperature
0–60° C (32–140° F)
Storage Temperature
-20 – 70° C (-4 – 158° F)
Relative Humidity
5–95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304

Table of Contents

Other manuals for AutomationDirect DL205

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect DL205 and is the answer not in the manual?

AutomationDirect DL205 Specifications

General IconGeneral
BrandAutomationDirect
ModelDL205
CategoryController
LanguageEnglish

Related product manuals