DL205 Analog Manual, 7th Edition Rev. D
16-15
Chapter 16: F2-8AD4DA-2, 8-Ch. In / 4-Ch. Out Analog Voltage Combination
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
D
Input Track and Hold Selection Bits
The track and hold feature for each of the eight inputs can be individually configured for
minimum, maximum, no hold, or reset held value. This configuration can be changed “on the
fly” while the program is running.
V36423: (specific memory location will vary depending upon the base and slot location).
TnH = Track and hold channel n High bit
TnL = Track and hold channel n Low bit
Example: Input channel track and hold settings: 1-3 = none, ch 4-5 = minimum, ch 6-7 =
maximum, ch 8 = reset; V36423=E940(hex).
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
C
D
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
T-
8H
T-
8L
T-
7H
T-
7L
T-
6H
T-
6L
T-
5H
T-
5L
T-
4H
T-
4L
T-
3H
T-
3L
T-
2H
T-
2L
T-
1H
T-
1L
Track and Hold Select TnH TnL Result
No Track and Hold 0 0 returns real time input value
Track and Hold Minimum Value 0 1 maintains lowest measured value
Track and Hold Maximum Value 1 0 maintains highest measured value
Reset Track and Hold Value 1 1 resets previously held input value
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
T-
8H
T-
8L
T-
7H
T-
7L
T-
6H
T-
6L
T-
5H
T-
5L
T-
4H
T-
4L
T-
3H
T-
3L
T-
2H
T-
2L
T-
1H
T-
1L
1 1 1 0 1 0 0 1 0 1 0 0 0 0 0 0
E 9 4 0

Table of Contents

Other manuals for AutomationDirect DL205

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AutomationDirect DL205 and is the answer not in the manual?

AutomationDirect DL205 Specifications

General IconGeneral
BrandAutomationDirect
ModelDL205
CategoryController
LanguageEnglish

Related product manuals