118 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
IEC 61850 COMMUNICATIONS CHAPTER 6: COMMUNICATIONS
GOOSE ETYPE APPID
Range: 0 to 16383 in steps of 1
Default: 0
This setting allows the selection of a specific application ID for each GOOSE sending
device. This value can be left at its default if the feature is not required. This setting is
required by IEC 61850.
GOOSE Minimum Time to Live
Range: 50 to 4000 ms in steps of 1
Default: 400 ms
This setting specifies the minimum time to live for the GOOSE transmission data set.
Configurable GOOSE transmission
The configurable GOOSE settings allow the D90
Plus
to be configured to transmit a number
of datasets within IEC 61850 GOOSE messages. Up to eight configurable datasets can be
configured and transmitted, allowing for optimization of data transfer between devices.
This is useful for intercommunication between D90
Plus
IEDs and devices from other
manufacturers that support IEC 61850.
Items programmed for datasets 1 through 8 have changes in their status transmitted once
per protection pass for digital data and every 250 ms for analog data.
The integrity GOOSE message is sent at the pre-configured rate for all datasets, even if no
changes in the data items are detected.
The configurable GOOSE feature is recommended for applications that require GOOSE
data transfer between UR
Plus
-series IEDs and devices from other manufacturers. Fixed
GOOSE is recommended for applications that require GSSE data transfer between UR
Plus
-
series IEDs. IEC 61850 GOOSE messaging contains a number of configurable parameters,
all of which must be correct for successful data transfer. It is critical that the configured
datasets at the transmission and reception devices are an exact match in terms of data
structure, and that the GOOSE addresses and name strings match exactly. Manual
configuration is possible, but third-party substation configuration software can be used to
automate the process. The UR
Plus
-series software can produce IEC 61850 ICD files and
import IEC 61850 SCD files produced by a substation configurator.
Select the Settings > Communications > IEC 61850 > GSSE/GOOSE Configuration >
Transmission > Tx Configurable GOOSE menu to open the configurable GOOSE
transmission configuration window.
Figure 96: Configurable GOOSE transmission configuration settings