CHAPTER 14: TESTING SELF-TESTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 625
SNTP ERROR FAILURE
Description: The SNTP server is not responding.
Severity: Protection is available. Timestamping of events can be inaccurate.
If this message appears, check that the SNTP server is operational and configured
correctly. Check for Ethernet LAN problems.
UNDEFINED RESULT
Description: An error has occurred during automation logic execution.
Severity: Automation logic execution is not suspended, and protection is still available.
Analyze and correct the automation logic equations.
Self-test logic operands
The following self-test logic operands are available for the D90
Plus
. They are listed
alphabetically by operand syntax.
Self-test error logic operands
AC SLOT F HIGH TEMP..............................
Asserted when the AC SLOT F HIGH TEMP self-test error
message is issued.
AC SLOT F TROUBLE..................................
Asserted when the AC SLOT F TROUBLE self-test error message
is issued.
AC SLOT J FMW MSMTCH.......................
Asserted when the AC SLOT J FIRMWARE MISMATCH self-test
error message is issued.
AC SLOT J HIGH TEMP..............................
Asserted when the AC SLOT J HIGH TEMP self-test error
message is issued.
AC SLOT J NOT CAL....................................
Asserted when the AC SLOT J NOT CALIBRATED self-test error
message is issued.
AC SLOT J TROUBLE ..................................
Asserted when the AC SLOT J TROUBLE self-test error message
is issued.
ANY MAJOR ERROR...................................
Asserted when any major self-test error message is issued.
ANY MINOR ERROR....................................
Asserted when any minor self-test error message is issued.
AUTOMATION LOGIC ERR........................
Asserted when the AUTOMATION LOGIC ERROR self-test error
message is issued.
CH1 DIR IO RING BRK ...............................
Asserted when the CH1 DIRECT IO RING BREAK self-test error
message is issued.
CH2 DIR IO RING BRK ...............................
Asserted when the CH2 DIRECT IO RING BREAK self-test error
message is issued.
CPU CARD TROUBLE .................................
Asserted when the CPU CARD TROUBLE self-test error message
is issued.
DELAYED AUTOMATION...........................
Asserted when the DELAYED AUTOMATION self-test error
message is issued.
EQUIPMENT MISMATCH...........................
Asserted when the EQUIPMENT MISMATCH self-test error
message is issued.
FILE SYSTEM TROUBLE.............................
Asserted when the FILE SYSTEM TROUBLE self-test error
message is issued.
FRONT PANEL MISMATCH.......................
Asserted when the FRONT PANEL MISMATCH self-test error
message is issued.
HIGH TEMPERATURE .................................
Asserted when the HIGH TEMPERATURE self-test error message
is issued.
IO SLOT E FMW MSMTCH........................
Asserted when the IO SLOT E FIRMWARE MISMATCH self-test
error message is issued.
IO SLOT E NOT CAL ....................................
Asserted when the IO SLOT E NOT CALIBRATED self-test error
message is issued.