CHAPTER 7: PROTECTION GROUPED PROTECTION ELEMENTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 183
Figure 161: Disturbance detector logic
Use of sources example
Consider a D90
Plus
connected as shown. This configuration can be used on a transmission
line connected into a breaker-and-a-half system. The figure shows the arrangement of
sources used to provide the functions required in this application, and the AC module
inputs used to provide the data.
Figure 162: Use of sources example
Grouped protection elements
Each protection element can be assigned up to six sets of settings with designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time.
Multiple setting groups allow the user to conveniently change protection settings for
different operating situations (for example, altered power system configuration or season
of the year). The active setting group can be preset or selected in the Settings > Protection
> Control > Setting Groups menu.
Line pickup
The line pickup feature uses a combination of undercurrent and undervoltage to identify a
line that has been de-energized (line end open). Alternately assign a FlexLogic operand to
the Terminal Open setting that specifies the terminal status. Three instantaneous
$&'5
25
$&78$/9$/8(
,B
6RXUFH
&XUUHQW3KDVRU
,B
,B
6(77,1*
_,B_²_,B_ !îFXWRIIŏ
&XUUHQW&XWRII/HYHO
_,B_²_,B_ !îFXWRIIŏ
_,B_²_,B_ !îFXWRIIŏ
ZKHUH_,B_
DUHWZRF\FOHVROG
ŏ ŏ ŏ_,B_ DQG_,B_
)/(;/2*,&23(5$1'
65&''23
$&'5
$&PRGXOH
EDQN
%) %)
3
*
$
9
:9DU
6RXUFH
6RXUFH
9ROWV
$PSV
-
-
-
6RXUFH
85
3OXV
VHULHV,('
$PSV
9ROWV
9ROWV
$PSV
3+
3+
3+
-
-