EasyManua.ls Logo

GE D90 Plus - Ground Directional Overcurrent Theory

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 15: THEORY OF OPERATION GROUND DIRECTIONAL OVERCURRENT THEORY
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 647
Consequently, the following signals are applied to the phase AB distance element:
Eq. 77
Eq. 78
This results in the following apparent impedance:
Eq. 79
The apparent impedance calculated in the equation is a correct measure of the distance
from the VT location to the fault. For relay location H, this certainly includes the positive-
sequence impedance of the transformer.
Eq. 80
Therefore, 0.127 90° + 0.05779 85° = 0.1847 88.4° on the primary side or 2.569
88.4° on the secondary side.
This example illustrates how the D90
Plus
maintains correct reach for fault behind power
transformers. When installed at location X, set the D90
Plus
reach to 0.687 85°
secondary to cover the fault shown in the figure. When installed at location H, set the
D90
Plus
reach to 2.569 88.4° to ensure exactly the same coverage.
Ground directional overcurrent theory
Consider the negative-sequence directional overcurrent element. As illustrated here, the
negative-sequence voltage can be low during internal fault conditions.
Figure 556: Offset impedance augmentation
²
%&$%
999
N9SULPDU\RU9VHFRQGDU\
²
%
,,
N$²SULPDU\RU$²VHFRQGDU\
,
9
=
$33
N9
N$²
űVHFRQGDU\
ű
î
N9
N9
09$

=
7
DWN9
=
/
DWN9 űî
N9
ű
$&'5

85 ,('
3OXV
9B!
,=Bî B
/,1(

,B
(&$
,=Bî
9B²B9
6BSRO
6BRS

,B
(&$
,=Bî
9B
² B9
6BSRO
6BRS

² B9
85 ,('
3OXV

Table of Contents

Other manuals for GE D90 Plus

Related product manuals