EasyManua.ls Logo

GE D90 Plus - Page 656

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
646 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PHASE DISTANCE APPLIED TO POWER TRANSFORMERS CHAPTER 15: THEORY OF OPERATION
Figure 555: Example system configuration
The D90
Plus
input signals at point X are shown in the following table.
Table 26: Input signals at point X for example system with power transformers
If installed at location X, the D90
Plus
uses the following input signals for its phase AB
distance element.
V = V
AB
= 77.402 kV 57.5° primary or 29.49 V 57.5° secondary.
I = I
A
I
B
= 2.576 kA –27.6° primary or 42.93 A –27.6° secondary.
And consequently, the D90
Plus
sees the following apparent impedance:
Z
APP
= V / I = 30.05 85° primary or 0.687 85° secondary
If applied at location H, the D90
Plus
input signals are shown in the following table.
Table 27: Input signals at point H for example system with power transformers
The following settings are applied in the D90
Plus
:
Transformer Voltage Connection: “Dy11”
Transformer Current Connection: “Dy11”
Input Primary Secondary
V
A
100.4 kV –7.32° 38.25 V –7.3
V
B
97.23 kV –53.4° 37.04 V –53.4°
V
C
181.8 kV –150.0° 69.26 V –150.0°
I
A
1.288 kA –27.6° 21.47 A –27.6°
I
B
1.288 kA 152.4° 21.47 A 152.4°
I
C
00
Input Primary Secondary
V
A
7.854 kV –5.59° 69.95 V –5.5
V
B
6.269 kV –120.1° 54.52 V –120.1°
V
C
7.751 kV 125.5° 65.84 V 125.5°
I
A
16.976 kA –27.6° 10.61 A –27.6°
I
B
33.952 kA 152.4° 21.11 A 152.4°
I
C
16.976 kA –27.6° 10.61 A –27.6°
$&'5
$%
Z\HODJ
 ű
 ű 
09$
N9N9
=
/
 ű
97 N99
&7 
97 N99
&7 
GHOWD
+;

Table of Contents

Other manuals for GE D90 Plus

Related product manuals