CHAPTER 6: COMMUNICATIONS IEC 61850 COMMUNICATIONS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 131
MMXU1 LN Prefix through MMXU4 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for measured quantity logical nodes 1 through 4.
PIOC1 LN Prefix through PIOC14 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for instantaneous overcurrent logical nodes 1
through 14.
PDIS1 LN Prefix through PDIS10 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for distance protection logical nodes 1 through 10.
PTOC1 LN Prefix through PTOC18 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for time overcurrent logical nodes 1 through 18.
PTOV1 LN Prefix through PTOV8 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for overvoltage logical nodes 1 through 8.
PTRC1 LN Prefix through PTRC2 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for the protection trip conditioning 1 through 2 logical
nodes.
PTUV1 LN Prefix through PTUV4 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for undervoltage logical nodes 1 through 4.
RBRF1 LN Prefix, RBRF2 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for breaker failure logical nodes 1 and 2.
RDIR1 LN Prefix, RDIR2 LN Prefix
Range: six character ASCII string
Default: empty
These settings specify the prefixes for the directional element logical nodes 1 and 2.
RFLO1 LN Prefix
Range: six character ASCII string
Default: empty
This setting specifies the prefix for the fault locator logical node.
RPSB1 LN Prefix
Range: six character ASCII string
Default: empty
This setting specifies the prefix for the power swing detection logical node.