EasyManua.ls Logo

GE D90 Plus - Page 165

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 6: COMMUNICATIONS DIRECT INPUTS AND OUTPUTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 155
Figure 126: Direct input and output settings for IED 1
For UR
Plus
-series IED 2:
Figure 127: Inter-relay communications settings for IED 2
Figure 128: Direct input and output settings for IED 2
The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is,
from device 1 to device 2, and from device 2 to device 1. Different communication cards
can be selected by the user for this back-to-back connection (for example: fiber, G.703, or
RS422).
Direct inputs and outputs for interlocking busbar protection
A simple interlocking busbar protection scheme can be accomplished by sending a
blocking signal from downstream devices, say 2, 3, and 4, to the upstream device that
monitors a single incomer of the busbar.

Table of Contents