EasyManua.ls Logo

GE D90 Plus - Page 188

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
178 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
POWER SYSTEM CHAPTER 7: PROTECTION
Calculating the power cut-off level
The Current Cutoff Level and the Voltage Cutoff Level settings are used to determine the
metered power cut-off levels. The power cut-off level is calculated as shown here. For delta
connections, the power cut-off is calculated as follows:
Eq. 4
where VT primary = VT secondary × VT ratio and CT primary = CT secondary × CT ratio.
For wye connections, the three-phase and per-phase power cut-off values are calculated
as follows:
Eq. 5
Eq. 6
where VT primary = VT secondary × VT ratio and CT primary = CT secondary × CT ratio.
For example, given the following settings:
Figure 157: Typical power system settings
we have:
CT primary =
Phase CT Ratio × Phase CT Secondary = 20 × 5 A = 100 A.
VT primary =
Phase VT Ratio × Phase VT Secondary = 208 × 66.4 V = 13811.2 V.
The power cut-off is therefore:
Eq. 7
Any calculated power value below this cut-off does not display. As well, the three-phase
energy data does not accumulate if the total power from all three phases does not exceed
the power cut-off.
7KUHHSKDVH
SRZHUFXWRII
î î î97SULPDU\î&7SULPDU\&XUUHQW&XWRII/HYHO 9ROWDJH&XWRII/HYHO
97VHFRQGDU\
7KUHHSKDVH
SRZHUFXWRII
97VHFRQGDU\
î î î97SULPDU\î&7SULPDU\&XUUHQW&XWRII/HYHO 9ROWDJH&XWRII/HYHO
3HUSKDVH
SRZHUFXWRII
97VHFRQGDU\
&XUUHQW&XWRII/HYHO 9ROWDJH&XWRII/HYHOî î97SULPDU\î&7SULPDU\
7KUHHSKDVH
SRZHUFXWRII
îSXî9î$î9
9
:
î î î97SULPDU\î&7SULPDU\&XUUHQW&XWRII/HYHO 9ROWDJH&XWRII/HYHO
97VHFRQGDU\

Table of Contents

Other manuals for GE D90 Plus

Related product manuals