CHAPTER 7: PROTECTION GROUPED PROTECTION ELEMENTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 219
Seal-In Delay
Range: 0.000 to 65.535 seconds in steps of 0.001
Default: 0.400 seconds
The out-of-step trip FlexLogic operand (POWER SWING TRIP) is sealed-in for the specified
period of time. The sealing-in is crucial in the delayed trip mode, as the original trip signal
is a very short pulse occurring when the impedance locus leaves the outer characteristic
after the out-of-step sequence is completed.
Trip Mode
Range: Early, Delayed
Default: Delayed
Selection of the “Early” trip mode results in an instantaneous trip after the last step in the
out-of-step tripping sequence is completed. The early trip mode stresses the circuit
breakers as the currents at that moment are high (the electromotive forces of the two
equivalent systems are approximately 180° apart). Selection of the “Delayed” trip mode
results in a trip at the moment when the impedance locus leaves the outer
characteristic. Delayed trip mode relaxes the operating conditions for the breakers as
the currents at that moment are low. Make the selection considering the capability of the
breakers in the system.
Block
Range: any FlexLogic operand
Default: Off
This setting selects the FlexLogic operand used for blocking the out-of-step function
only. The power swing blocking function is operational all the time as long as the
element is enabled. The blocking signal resets the output POWER SWING TRIP operand but
does not stop the out-of-step tripping sequence.
Events
Range: Enabled, Disabled
Default: Enabled
This setting enables and disables the logging of power swing detect events in the
sequence of events recorder.
Figure 192: Power swing detect scheme logic, sheet 1 of 3
$&'5
$1'
$1'
$1'
6RXUFH
6(77,1*
9B
,B
)XQFWLRQ
6(77,1*
(QDEOHG
'LVDEOHG
6KDSH
6(77,1*6
6KDSH
4XDGULODWHUDO5HYHUVH0LGGOH
4XDGULODWHUDO5HYHUVH2XWHU
5HYHUVH5&$
5XQ
287(5,03('$1&(5(*,21
==0DJQLWXGH
==$QJOH
)RUZDUG5HDFK
4XDGULODWHUDO)RUZDUG0LGGOH
4XDGULODWHUDO)RUZDUG2XWHU
)RUZDUG5&$
5HYHUVH5HDFK
2XWHU/LPLW$QJOH
6KDSH
0LGGOH/HIW%OLQGHU
,QQHU5LJKW%OLQGHU
,QQHU/HIW%OLQGHU
==0DJQLWXGH
==$QJOH
0LGGOH/LPLW$QJOH
,QQHU/LPLW$QJOH
2XWHU5LJKW%OLQGHU
2XWHU/HIW%OLQGHU
0LGGOH5LJKW%OLQGHU
5XQ
0,''/(,03('$1&(5(*,21
5XQ
,11(5,03('$1&(5(*,21
6XSHUYLVLRQ
6(77,1*
5XQ
_,B_!3LFNXS
32:(56:,1*,11(5
)/(;/2*,&23(5$1'
32:(56:,1*0,''/(
)/(;/2*,&23(5$1'
32:(56:,1*287(5
)/(;/2*,&23(5$1'

Table of Contents

Other manuals for GE D90 Plus

Related product manuals