EasyManua.ls Logo

GE D90 Plus - Page 272

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
262 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
GROUPED PROTECTION ELEMENTS CHAPTER 7: PROTECTION
validated, neither forward nor reverse indication is given. In addition, the negative-
sequence current (or zero-sequence current) must be greater than the
Current Cutoff Level
setting value specified in the Protection > Power System > AC Inputs – Current menu. The
following figure explains the usage of the voltage polarized directional unit of the element.
Figure 224: Negative-sequence directional characteristics
The forward-looking function is designed to be more secure as compared to the reverse-
looking function, so use the forward-looking function for the tripping direction. The
reverse-looking function is faster compared to the forward-looking function and is to be
used for the blocking direction. This allows for better protection coordination. Take this bias
into account when using the negative-sequence directional overcurrent element to
directionalize other protection elements.
Select the Settings > Protection > Elements > Group 1 > Current > Negative Sequence
Directional OC menu to open the negative-sequence directional overcurrent
configuration window.
$&'5
9$*UHIHUHQFH
9&*
9%*
,BOLQH
,BOLQH
(&$OLQH
²(&$OLQH
/LPLWDQJOH
/LPLW
DQJOH
/LPLWDQJOH
/LPLW
DQJOH
(&$
)RUZDUGRSHUDWLQJ
UHJLRQ
5HYHUVH
RSHUDWLQJUHJLRQ
)RUZDUG
OLPLWDQJOH
)RUZDUG
OLPLWDQJOH
5HYHUVH
OLPLWDQJOH
5HYHUVH
OLPLWDQJOH
9BOLQH
9BOLQH

Table of Contents

Other manuals for GE D90 Plus

Related product manuals