EasyManua.ls Logo

GE D90 Plus - Page 30

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION
FLEXCURVES™
Number: .................................................................. 4 (A through D)
Reset points:.......................................................... 40 (0 through 1 of pickup)
Operate points:....................................................80 (1 through 20 of pickup)
Time delay: ............................................................0 to 65535 ms in steps of 1
FLEXELEMENTS™
Elements:................................................................ 16
Operating signal: ................................................any analog actual value, or two values in differential mode
Operating signal mode:................................... signed or absolute value
Operating mode:.................................................level, delta
Comparator detection: ....................................over, under
Pickup level:...........................................................–90.000 to 90.000 pu in steps of 0.001
Hysteresis:..............................................................0.1 to 50.0% in steps of 0.1
Delta dt:................................................................... 20 ms to 60 days
Pickup delay:.........................................................0.000 to 65.535 seconds in steps of 0.001
Dropout delay: .....................................................0.000 to 65.535 seconds in steps of 0.001
FLEXMATRIX
Principle: .................................................................aggregates and conditions signals for tripping and auxiliary
functions
Timing accuracy: ................................................±1 ms
FLEX STATES
Number: .................................................................. up to 256 logical variables grouped under 16 Modbus
addresses
Programmability: ................................................any logical variable, contact, or virtual input
GROUND DISTANCE
Characteristic:......................................................mho (memory polarized or offset) or quad (memory polarized
or non-directional), selectable individually per zone
Reactance polarization:...................................negative-sequence or zero-sequence current
Non-homogeneity angle:................................–40 to 40° in steps of 1
Zones:....................................................................... 5
Directionality:........................................................forward, reverse, or non-directional per zone
Reach (secondary ohms):................................0.02 to 250.00 ohms in steps of 0.01
Reach accuracy: ................................................. ±5%, including the effect of CVT transients up to an SIR of 30
for V < 1.1 × V
nominal
Distance characteristic angle:......................30 to 90° in steps of 1
Comparator limit angle: ..................................30 to 90° in steps of 1
Characteristic angle:.........................................30 to 90° in steps of 1
Limit angle: ............................................................30 to 90° in steps of 1
Z0/Z1 magnitude:...............................................0.00 to 10.00 in steps of 0.01
Z0M/Z1 angle: ......................................................–90 to 90° in steps of 1
Z0M/Z1 magnitude:...........................................0.00 to 7.00 in steps of 0.01
Z0/Z1 angle: ..........................................................–90 to 90° in steps of 1
Right and left blinder reach:..........................0.02 to 500.00 ohms in steps of 0.01
Right and left blinder characteristic
angle: ..................................................................60 to 90° in steps of 1
Time delay: ............................................................0.000 to 65.535 seconds in steps of 0.001
Timing accuracy: ................................................±3% or 4 ms (whichever is greater)
Current supervision level: ...............................neutral current (3I_0)
Current supervision pickup:........................... 0.050 to 30.000 pu in steps of 0.001
Memory duration:...............................................5 to 25 cycles in steps of 1
Voltage supervision pickup:...........................0 to 5.000 pu in steps of 0.001 (series compensation
applications)
Operation time:....................................................1 to 1.5 cycles (typical)
Reset time: ............................................................. 1 power cycle (typical)