EasyManua.ls Logo

GE D90 Plus - Page 325

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 7: PROTECTION CONTROL ELEMENTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 315
RX1, RX2, RX3, RX4
Range: any FlexLogic operand
Default: OFF
These settings select FlexLogic operands to represent the permission receive signals for
the scheme. Contact inputs interfacing with a signaling system typically are used. These
settings must be used in conjunction with the loss-of-guard signals, otherwise the
scheme does not unblock and thus fails to operate. These settings are used as follows:
In single-bit applications,
RX1 must be used
In two-bit applications,
RX1 and RX2 must be used
In four-bit applications,
RX1 through RX4 must be used
Loss of Guard 1, Loss of Guard 2, Loss of Guard 3, Loss of Guard 4
Range: any FlexLogic operand
Default: OFF
These settings select FlexLogic operands to represent the loss-of-guard receive signals
for the scheme. Contact inputs interfacing with a signaling system typically are used.
Each loss-of-guard signal must correspond to the same receive signal from the same
communications channel (that is,
RX1 and Loss of Guard 1 must be from the same
communications channel, and the same for channels 2, 3 and 4, if used). These settings
are used as follows:
In single-bit applications,
Loss of Guard 1 and RX1 must be used
In two-bit applications,
Loss of Guard 1 with RX1 and Loss of Guard 2 with RX2
must be used
In four-bit applications, all receive and loss-of-guard signals must be used
Events
Range: Enabled, Disabled
Default: Enabled
This setting enables and disables the logging of directional comparison unblocking
scheme events in the sequence of events recorder.
The figures show the directional comparison unblocking scheme logic.

Table of Contents

Other manuals for GE D90 Plus

Related product manuals