EasyManua.ls Logo

GE D90 Plus - Page 336

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
326 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS CHAPTER 7: PROTECTION
Figure 267: Trip output configuration settings
The following settings are available.
Trip Mode
Range: Disabled, 3 Pole Only, 3 Pole & 1 Pole
Default: Disabled
This setting selects the required mode of operation. If selected to “3 Pole Only,” outputs
for all three phases are always set simultaneously. If selected to “3 Pole & 1 Pole,”
outputs for all three phases are set simultaneously unless the phase selector or a pilot
aided scheme determines the fault is single-phase-to-ground. If the fault is identified as
being AG, BG, or CG only the operands for the faulted phase are asserted.
Trip 3-Pole Input 1, Trip 3-Pole Input 2, Trip 3-Pole Input 3, Trip 3-Pole Input 4, Trip 3-
Pole Input 5, Trip 3-Pole Input 6
Range: any FlexLogic operand
Default: OFF
These settings select an operand representing an unwanted fault condition to initiate a
single pole operation (for example, phase undervoltage). A FlexLogic OR-gate can be
used if more than six inputs are required.
Trip 1-Pole Input 1, Trip 1-Pole Input 2, Trip 1-Pole Input 3, Trip 1-Pole Input 4, Trip 1-
Pole Input 5, Trip 1-Pole Input 6
Range: any FlexLogic operand
Default: OFF
These settings select an operand representing a fault condition that is required to initiate
a single pole trip-and-reclose if the fault is single phase to ground (for example, phase
distance zone 1). Use a FlexLogic OR-gate if more than six inputs are required. The inputs
do not have to be phase-specific, as the phase selector determines the fault type.

Table of Contents

Other manuals for GE D90 Plus

Related product manuals