354 D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS CHAPTER 7: PROTECTION
Figure 299: Autoreclose settings window
The following settings are available.
Function
Range: Disabled, Enabled
Default: Disabled
This setting enables and disables the autoreclose scheme.
Mode
Range: 1 & 3 Pole, 1 Pole, 3 Pole-A, 3 Pole-B
Default: 1 & 3 Pole
This setting selects the autoreclose operating mode, which functions in conjunction with
signals received at the initiation inputs.