CHAPTER 7: PROTECTION PROTECTION INPUTS AND OUTPUTS
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 387
Figure 327: Protection virtual output settings
The following settings are available for each protection virtual output. If not assigned, the
virtual output is forced to off (logic 0).
ID
Range: up to 12 alphanumeric characters
Default: Virt Op 1
This setting specifies an identifier that can be assigned to each protection virtual output.
Events
Range: Enabled, Disabled
Default: Disabled
When this setting is “Enabled,” every change in the protection virtual output state
triggers an event in the sequence of events recorder.
Protection virtual output actual values
Select the Actual Values > Protection > Protection Inputs/Outputs > Virtual Outputs
menu to open the protection virtual outputs actual values window.
Figure 328: Protection virtual output actual values
The following actual values are available for all configured protection virtual outputs.
Name
Range: up to 12 alphanumeric characters
This value displays the programmed
ID for the corresponding protection virtual output.