CHAPTER 7: PROTECTION PROTECTION FLEXLOGIC
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 421
NEG SEQ DIR OC2 REV .............................
Asserted when the negative-sequence directional overcurrent
2 element reverse mode operates.
Negative-sequence instantaneous overcurrent operands
NEG SEQ IOC1 DPO ...................................
Asserted when the negative-sequence instantaneous
overcurrent 1 element drops out.
NEG SEQ IOC1 OP.......................................
Asserted when the negative-sequence instantaneous
overcurrent 1 element operates.
NEG SEQ IOC1 PKP ....................................
Asserted when the negative-sequence instantaneous
overcurrent 1 element picks up.
NEG SEQ IOC2..............................................
The operands listed above are also available for negative-
sequence instantaneous overcurrent 2.
Negative-sequence overvoltage operands
NEG SEQ OV DPO .......................................
Asserted when the negative-sequence overvoltage element
drops out.
NEG SEQ OV OP...........................................
Asserted when the negative-sequence overvoltage element
operates.
NEG SEQ OV PKP ........................................
Asserted when the negative-sequence overvoltage element
picks up.
Negative-sequence time overcurrent operands
NEG SEQ TOC1 DPO..................................
Asserted when the negative-sequence time overcurrent 1
element drops out.
NEG SEQ TOC1 OP .....................................
Asserted when the negative-sequence time overcurrent 1
element operates.
NEG SEQ TOC1 PKP ...................................
Asserted when the negative-sequence time overcurrent 1
element picks up.
NEG SEQ TOC2.............................................
The operands listed above are also available for negative-
sequence time overcurrent 2.
Neutral instantaneous overcurrent operands
NEUTRAL IOC1 DPO ..................................
Asserted when the neutral instantaneous overcurrent 1
element drops out.
NEUTRAL IOC1 OP......................................
Asserted when the neutral instantaneous overcurrent 1
element operates.
NEUTRAL IOC1 PKP....................................
Asserted when the neutral instantaneous overcurrent 1
element picks up.
NEUTRAL IOC2 to 12.................................
The operands listed above are also available for neutral
instantaneous overcurrent 2 through 12.
Neutral overvoltage operands
NEUTRAL OV1 DPO....................................
Asserted when the neutral overvoltage 1 element drops out.
NEUTRAL OV1 OP .......................................
Asserted when the neutral overvoltage 1 element operates.
NEUTRAL OV1 PKP.....................................
Asserted when the neutral overvoltage 1 element picks up.
NEUTRAL OV2 to 3.....................................
The operands listed above are also available for neutral
overvoltage 2 and 3.
Neutral time overcurrent operands
NEUTRAL TOC1 DPO .................................
Asserted when the neutral time overcurrent 1 element drops
out.
NEUTRAL TOC1 OP.....................................
Asserted when the neutral time overcurrent 1 element
operates.
NEUTRAL TOC1 PKP ..................................
Asserted when the neutral time overcurrent 1 element picks up.