AUTOMATION LOGIC CHAPTER 8: AUTOMATION
Selector switch operands
SELECTOR 1 ALARM ..................................
Asserted when the position of selector 1 has been pre-selected
but not acknowledged.
SELECTOR 1 BIT 0.......................................
Represents the first bit of the three-bit word encoding position
of selector 1.
SELECTOR 1 BIT 1.......................................
Represents the second bit of the three-bit word encoding
position of selector 1.
SELECTOR 1 BIT 2.......................................
Represents the third bit of the three-bit word encoding position
of selector 1.
SELECTOR 1 BIT ALARM...........................
Asserted when the position of selector 1 has been pre-selected
with the three-bit control input but not acknowledged.
SELECTOR 1 POS 1.....................................
Asserted when selector switch 1 is in position 1.
SELECTOR 1 POS 2.....................................
Asserted when selector switch 1 is in position 2.
SELECTOR 1 POS 3.....................................
Asserted when selector switch 1 is in position 3.
SELECTOR 1 POS 4.....................................
Asserted when selector switch 1 is in position 4.
SELECTOR 1 POS 5.....................................
Asserted when selector switch 1 is in position 5.
SELECTOR 1 POS 6.....................................
Asserted when selector switch 1 is in position 6.
SELECTOR 1 POS 7.....................................
Asserted when selector switch 1 is in position 7.
SELECTOR 1 PWR ALARM.......................
Asserted when the position of selector switch 1 is
undetermined or restored from memory when the relay powers
up and synchronizes to the three-bit input.
SELECTOR 1 STP ALARM..........................
Asserted when the position of selector 1 has been pre-selected
with the stepping up control input but not acknowledged.
SELECTOR 2... ...............................................
The same set of operands shown above are available for
selector switch 2.
Synchrocheck operands
SYNC 1 CLS DPO.........................................
Asserted when the synchrocheck 1 close has dropped out.
SYNC 1 CLS OP ............................................
Asserted when the synchrocheck 1 close has operated.
SYNC 1 DEAD S DPO.................................
Asserted when the synchrocheck 1 dead source has dropped
out.
SYNC 1 DEAD S OP ....................................
Asserted when the synchrocheck 1 dead source has operated.
SYNC 1 SYNC DPO .....................................
Asserted when the synchrocheck 1 has dropped out while in
synchronization.
SYNC 1 SYNC OP.........................................
Asserted when the synchrocheck 1 has operated while in
synchronization.
SYNC 1 V1 ABOVE MIN.............................
Asserted when the synchrocheck 1 V
1
value is above the
minimum live voltage.
SYNC 1 V1 BELOW MAX ..........................
Asserted when the synchrocheck 1 V
1
value is below the
maximum dead voltage.
SYNC 1 V2 ABOVE MIN.............................
Asserted when the synchrocheck 1 V
2
value is above the
minimum live voltage.
SYNC 1 V2 BELOW MAX ..........................
Asserted when the synchrocheck 1 V
2
value is below the
maximum dead voltage.
SYNC 2... .........................................................
The set of operands shown above are available for
synchrocheck 2.