EasyManua.ls Logo

GE D90 Plus - Page 547

GE D90 Plus
688 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 11: METERING PHASOR MEASUREMENT UNIT
D90
PLUS
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 537
Figure 467: Phasor Measurement Unit communications configuration
The following settings are available for the communication port on each PMU.
Type
Range: None, Network
Default: None
This setting specifies the first communication port for transmission of the PMU data. The
three ports are configured under individual menus.
PHS-1, PHS-2, PHS-3,..., PHS-14
Range: Off, Va, Vb, Vc, Vx, Ia, Ib, Ic, Ig, V1, V2, V0, I1, I2, I0
Default: Off
These settings select synchrophasors to be transmitted from the superset of all
synchronized measurements. The available synchrophasor values are
Va — The first voltage channel, either Va or Vab
Vb — The second voltage channel, either Vb or Vbc
Vc — The third voltage channel, either Vc or Vca
Vx — The fourth voltage channel
Ia — Phase A current, physical channel, or summation as per the source settings
Ib — Phase B current, physical channel, or summation as per the source settings
Ic — Phase C current, physical channel, or summation as per the source settings

Table of Contents

Other manuals for GE D90 Plus

Related product manuals