Configuration Parameter Definitions
Auxiliary Output Set Up Group
110 DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual Release M
April 2017
Upper Display
Range of Setting or Selection
SETPOINT 1—Represents the value of the setpoint in
units of PV for Loop 1.
PROCESS VARIABLE 2—Represents the value of the
process variable for Loop 2.
DEVIATION 2 (PROCESS VARIABLE MINUS
SETPOINT)—Represents –100 to +100% of the
selected PV span for Loop 2.
OUTPUT 2—Represents the displayed controller output
in percent (%) for Loop 2.
SETPOINT 2—Represents the value of the setpoint in
units of PV for Loop 2.
Low Scale Value
within the range of the selected
variable to represent 4 mA
AUXILIARY OUTPUT LOW SCALING FACTOR—Use
a value in engineering units for all selections above
except Output.
Use value in percent (%) for Output. (Output can be
between –5 and +105%.)
High Scale Value
within the range of the selected
variable to represent 20 mA
AUXILIARY OUTPUT HIGH SCALING FACTOR—Use
a value in engineering units for: Input 1, Input 2,
Process Variable, Deviation,* and Setpoint.
Use a value in percent (%) for Output. (Output can be
between –5 and +105%.)
*When Deviation is selected, only one operating
parameter will be entered. This value represents the
deviation level that will produce 20 mA output. Zero
deviation will produce a center scale (12 mA) output. A
negative deviation equal in magnitude to the Auxiliary
Output High Value will produce a low end (4 mA) output.
Repeat for AUX OUT 2 and AUX OUT 3.