ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Copyright © Huawei Technologies Co., Ltd.
5. Choose Monitoring > System > Independent Deployment AI_DI Unit Group >
Independent Deployment AI_DI1 Unit > Running Parameters > AI/DI_1 Port
Settings.
6. Set Door1 sensor to Enable and click Submit.
7. Set Door1 sensor type to Door sensor, ensure that Door1 power supply is Yes, and
click Submit.
8. Perform the preceding operations to set parameters for ports AI/DI_2 to AI/DI_8.
Step 2 Check the door status sensor functions.
Table 6-7 Function check
Door1 DI alarm is generated on the active alarm page
of the app or WebUI.
----End
6.4.1.2 Commissioning a Door Status Sensor (Connected to the AI/DI Port
on the Rack Environment Unit)
If a door status sensor is installed, perform the following steps to configure it.
Context
If the sensor is prefabricated, only check its settings.
If multiple door status sensors are connected, commission one door status sensor first
and then commission the other door status sensors in the same way.
Procedure
Step 1 Choose Monitoring > Cabinet > IT Cabinet1 > Cabinet Collector1 > Running
Parameters, set the door status sensor parameters.
Table 6-8 Parameter settings
Front door
status
(AI/DI_1)
1. Choose AI/DI_1 sensor to Enable, click Submit.
2. Set AI/DI_1 sensor type to Door sensor, click Submit.
Rear door
status
(AI/DI_2)
1. Choose AI/DI_2 sensor to Enable, click Submit.
2. Set AI/DI_2 sensor type to Door sensor, click Submit.
Step 2 Check the door status sensor functions.