ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Copyright © Huawei Technologies Co., Ltd.
273
The cleared alarm is displayed in the historical alarm list.
----End
8.1.14 How Can I View Performance Data?
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose Query > Performance Data.
Step 3 Set Device, Performance Data, Statistics Mode, Start time, and End Time, and click
Query.
The query result can be displayed in Table or Curve mode.
----End
8.1.15 How Is a Signal Name Changed?
Context
In this example, the smoke sensor is connected to the AI/DI_3 port on the ECC800-Pro.
The following procedure describes how to change the signal name of AI/DI_3. Other
signal names can be changed in a similar way.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Signal Name Modify. The Batch Signal Configuration page is
displayed.
Step 3 Set Device type to ECC800, set Device name to ECC800, and click OK.
Step 4 On the query result tab page, set the new signal name of AI/DI_3 to Smoke and click
Submit.
Step 5 Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_3 Port Settings.
Check that the signal name of AI/DI_3 has been changed to Smoke.
----End
8.1.16 How Can I Export Historical Data and Device Data?
Context
Export Historical Data: You can export historical alarms, active alarms, performance data,
operation logs, and access events of the system for viewing and analyzing events.
Export Device Data: You can export device data in system.