ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Copyright © Huawei Technologies Co., Ltd.
control module is
interrupted.
UIM20A expansion module
is normal, whether the board
is faulty, and whether the
UIM20A expansion module
is added on the ECC800-Pro
WebUI.
An alarm whose default
severity is major exists.
Check and clear the alarm.
Table 7-6 Common faults and troubleshooting for the independent deployment AI_DI unit
The PWR indicator is off.
The independent
deployment AI_DI unit is
faulty or the power to the
independent deployment
AI_DI unit is abnormal.
Check whether the board is
faulty and whether the cable
connection between the
ECC800-Pro and
independent deployment
AI_DI unit is normal.
The RUN indicator is off.
The contact between the
independent deployment
AI_DI unit and the
ECC800-Pro is abnormal, or
the independent deployment
AI_DI unit is faulty.
Check whether the
independent deployment
AI_DI unit is faulty and
whether the cable
connection between the
ECC800-Pro and
independent deployment
AI_DI unit is normal.
The RUN indicator is
blinking at short intervals
(on for 0.125s and then off
for 0.125s).
Communication between the
independent deployment
AI_DI unit and the main
control module is
interrupted.
Check whether the cable
connection between the
ECC800-Pro and
independent deployment
AI_DI unit is normal,
whether the independent
deployment AI_DI unit is
faulty, and whether the
independent deployment
AI_DI unit is added on the
ECC800-Pro WebUI.
An alarm whose default
severity is major exists.
Check and clear the alarm.
7.3 Component Replacement
1. After replacing components, log in to the WebUI and choose Maintenance >
Parameter Sync to access the parameter synchronization page.