ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Copyright © Huawei Technologies Co., Ltd.
272
Step 7 Click Select in the Output Dry Contact column corresponding to Operation log full as
required, select Yes or No for DO, and click OK.
Step 8 Click Select in the Loudspeaker column corresponding to Operation log full as required, set
Loudspeaker to Yes or No, and click OK.
----End
8.1.12 How Can I View Real-Time Monitoring Data, Active
Alarms, Historical Alarms, Access Event, and Operation Logs?
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Click Monitoring, select the device to be viewed, and select Running Info to view the
real-time data of the device.
Step 3 Choose Home > Active Alarms to view the active alarms of the ECC800-Pro. Click Details
in the Alarm Details area to view alarm details of devices.
Step 4 Choose Query to view the historical alarms, access events, and operation logs of the device.
1. View historical alarms, choose Query > Historical Alarms. Set Device, Start time,
End time, Sort mode and Sorting By, and click Query.
2. To view access events, choose Query > Access Event.
3. To view operation logs, choose Query > Operation Log.
----End
8.1.13 How Can I Handle Alarms?
Procedure
Step 1 Log in to the ECC800-Pro WebUI.
Step 2 Choose Home > Active Alarms and view active alarms.
Step 3 Select an alarm to be acknowledged and click Confirm.
Figure 8-23 Acknowledging an alarm
Step 4 Handle an alarm based on the alarm information.
Step 5 Select an alarm to be cleared and click Clear Alarm.