ECC800 Data Center Controller
User Manual (for ECC800-Pro)
6 Feature Description
Copyright © Huawei Technologies Co., Ltd.
131
Table 6-16 Function commissioning
Check Method
Normal Connection Status
Attempt to open the door by pressing the
skylight button when the aisle door is
closed.
The skylight can be opened manually.
Step 3 Check functions of the atmosphere light.
Table 6-17 Function commissioning
Check Method
Normal Connection Status
Press the atmosphere light
button.
The atmosphere light is steady blue.
Step 4 Check functions of the emergency button.
Table 6-18 Function commissioning
Check Method
Normal Connection
Status
Follow-up Procedure
Attempt to open the door by
pressing the emergency button
when the aisle door is closed.
The aisle door is
opened successfully.
You need to restore the
emergency button.
Step 5 Check functions of the magnetic lock.
Table 6-19 Function commissioning
Check Method
Normal Connection
Status
Troubleshooting
When the aisle door is
normally closed, check
whether there is a door open
alarm on the ECC800-Pro.
There is no door open
alarm on the
ECC800-Pro.
If a door open alarm is reported
when the door is closed,
relocate the magnetic lock and
magnet to minimize the
deviation until the door open
alarm is cleared.
----End