ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Copyright © Huawei Technologies Co., Ltd.
SNMP version and port number used by the
ECC800-Pro and NMS. The SNMP versions include
SNMPv1, SNMPv2c, and SNMPv3.
Read community
name
Write community
name
If you use SNMPv1 or SNMPv2c, enter the read and
write community names that comply with the NMS.
Otherwise, the ECC800-Pro will not connect to the
NMS. The read community name must be different
from the write community name.
User name
MD5/SHA
password
DES/AES
password
To enhance the security, you need a user name and
password for authentication if you use SNMPv3.
After the authentication succeeds, the ECC800-Pro
can communicate with the NMS.
IP address of the NMS server.
Port defined by the user.
Context
SNMPv3 parameters should be set before connecting the ECC800-Pro to the NMS.
These parameters are required for setting up the ECC800-Pro on the NMS.
SNMPv1 and SNMPv2c are insecure. Therefore, SNMPv3 is recommended. This
section uses SNMPv3 as an example.
Procedure
Step 1 Apply to the equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 6-51 IP parameters
System
Settings >
System
Parameters
> Monitor
IP >
WAN_1
Set this parameter based on the IP address
assigned by the network administrator.
Set this parameter based on the subnet mask
assigned by the network administrator.
Set this parameter based on the default
gateway address assigned by the network
administrator.
Step 3 Set SNMP parameters.