EasyManua.ls Logo

Huawei ECC800 - Page 240

Huawei ECC800
321 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
8 FAQ
Copyright © Huawei Technologies Co., Ltd.
229
Figure 8-9 UPS5000-E communication settings
Step 2 Add a UPS5000-E.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a UPS5000-E.
Table 8-4 Adding a UPS5000-E
Path
Parameter
Name
Setting
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
Device attribute
Select UPS from the drop-down list box.
Device Type
Select UPS5000 from the drop-down list box.
Connect To
Select ETH Converter n from the drop-down list
box.
Communications
Port
Select COM1/COM2 from the drop-down list box.
Device Address
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
UPS5000-E based on the actual situation.
3. Click Test Connect to check whether the UPS5000-E connects to the ECC800-Pro
properly.
If the UPS5000-E connects to the ECC800-Pro properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the UPS5000-E does not connect to the ECC800-Pro properly, check whether the
cable between the UPS5000-E and the ECC800-Pro is connected properly, whether
the UPS5000-E and ECC800-Pro are running properly, and whether the input
parameters are consistent with the UPS5000-E parameters.
4. Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter n_Device name.
----End

Table of Contents

Related product manuals