Batt. String
Cong
Description
Current
acquisition source
The actual specications of the Hall eect sensor
prevail.
Battery N line Set whether there is a battery N wire according to the
actual situation.
Single batt. group
number of HALL
Indicates the number of Hall eect sensors connected
to a single battery string.
Single batt.
capacity
Species the capacity of each battery that is connected
in the battery string in series.
Batt. installation
time
Time when the battery is installed for the rst time.
Does not need to be reset when part of batteries are
replaced.
iBAT number of
iBOX
Indicates the total number of iBATs managed by the
iBOX.
Number of
battery strings
Indicates the total number of battery strings managed
by the iBOX.
Batt. string No. Sets the battery string numbers of the iBOXs connected
in parallel to unique ones when multiple iBOXs are
connected in parallel.
6. On the iBOX WebUI, choose System Settings > Running Parameter, and set
Running Parameter.
Figure 6-12 Running Parameter
Running
Parameter
Description
Parallel
Communication
Conguration
There is no need to set this parameter for a single
iBOX. If multiple iBOXs are connected in parallel, set
iBOX parallel communication switch to Yes, set
Number of iBOX congured under each UPS, and set
the IP address for each iBOX.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 160