EasyManua.ls Logo

Huawei iMaster NetEco V600R021C10 - Page 209

Huawei iMaster NetEco V600R021C10
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 6-42 Setting SNMP trap parameters
Step 4 Add a user and set user permissions on the WebUI (WebUI 2).
1. Choose Congure > SNMP.
2. Select SNMPv3 for SNMP version, enter 161 for SNMP port, and click
Conrm.
Figure 6-43 Setting SNMP parameters
3. Click Add in SNMP.
Figure 6-44 Setting SNMP parameters_02
4. In the displayed Add SNMPv3 User dialog box, set related parameters and
click Add.
You are advised to set MD5/SHA Password and DES/AES Password to
dierent values.
MD5 is an insecure protocol. SHA is recommended. DES is an insecure
protocol. AES is recommended.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 198

Table of Contents

Related product manuals