3. In the SNMPv3 area, click Add.
4. In the displayed SNMPv3 dialog box, set SNMPv3 parameters, and click
Conrm.
You are advised to set MD5/SHA password and DES/AES password to
dierent values.
MD5 is an insecure protocol. SHA is recommended. DES is an insecure
protocol. AES is recommended.
Record the User Name, MD5/SHA password, and DES/AES password for
using when creating a UPS on the NetEco.
Figure 6-41 Setting SNMPv3 parameters
5. In the SNMP Trap area, click Add.
6. In the displayed SNMP Trap dialog box, set SNMP trap parameters, and click
Conrm.
Enter the IP address of the NetEco server in the Trap Target Address text
box.
Set Trap Port to 162.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 197