EasyManua.ls Logo

Huawei iMaster NetEco V600R021C10 - Page 212

Huawei iMaster NetEco V600R021C10
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Record the User Name, MD5/SHA password, and DES/AES password for
using when creating a UPS on the NetEco.
Figure 6-47 Setting SNMPv3 parameters
5. In the SNMP Trap area, click Add.
6. In the displayed SNMP Trap dialog box, set SNMP trap parameters, and click
Conrm.
Enter the IP address of the NetEco server in the Trap Target Address text
box.
Set Trap Port to 162.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 201

Table of Contents

Related product manuals