Figure 6-48 Setting SNMP trap parameters
Step 4 Add a user and set user permissions on the WebUI (WebUI 2).
1. Choose Congure > SNMP.
2. Select SNMPv3 for SNMP version, enter 161 for SNMP port, and click
Conrm.
Figure 6-49 Setting SNMP parameters
3. Click Add in SNMP.
Figure 6-50 Setting SNMP parameters_02
4. In the displayed Add SNMPv3 User dialog box, set related parameters and
click Add.
You are advised to set MD5/SHA Password and DES/AES Password to
dierent values.
MD5 is an insecure protocol. SHA is recommended. DES is an insecure
protocol. AES is recommended.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 202