Figure 6-54 Setting SNMP trap parameters
Step 4 Add a user and set user permissions on the WebUI (WebUI 2).
1. Choose Cong. > Site Cong..
2. In the SNMP area, set SNMP version to SNMPv3, and set SNMP port to 161.
Figure 6-55 Setting SNMP parameters
3. Click Add in SNMP.
Figure 6-56 Setting SNMP parameters_02
4. Set User name, MD5/SHA Password, and DES/AES Password for the user to
be added.
– You are advised to set MD5/SHA password and DES/AES password to
dierent values.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 206