v 2.3 — September 2015 Altanium Delta3
218 Alarm: Position Deviation Limit Exceeded
Maintenance pin(s) not removed before operation (Gen1 tools only)
Force limit set too low to complete the motion.
To troubleshoot this fault:
Review the concurrent alarms on the alarm page or in the Event log to determine when
the fault occurred. Was it during opening, closing, or while holding an end position?
Increase the closing and opening force limits to maximum
Reduce the speed, acceleration and deceleration settings
Increase the Position Alarm Window setting.