v 2.3 — September 2015 Altanium Delta3
72 Changing Multiple Zones Names
7.5.10.1 Changing Multiple Zones Names
Use the Auto+ button to rename and number multiple zones. The Auto+ button will number
the selected zones from 001 to n, where n is the number of zones selected. For example, if
renaming 7 zones, the Auto+ button will rename the zones sequentially from 001 to 007.
To number and rename multiple zones, do the following:
1. Select the zones to be renamed.
2. Touch the Zone Name field and enter a new zone name for all the selected zones.
To select commonly used zone names, use the following keys:
• zone
• probe
• tip
• nozzle
• sprue
• manifold
• bridge
• valve gate
• not used
3. To rename and number all the selected zones, touch the Auto+ button.
7.5.11 Changing a Setpoint
The setpoint temperatures for each of the heaters in the mold must be specified. The default
setting is 177 °C (350 °F).
To change a setpoint of a zone:
1. Touch the zone to be changed.
2. Touch the desired setpoint field and enter a new setpoint value
3. Touch the Accept button.
7.5.12 Changing the Alarm Window
Specify how many degrees above or below the setpoint to initiate the alarm. The default
setting is 6 °C (10 °F).
Alarm Example: Setpoint = 300 °F, Alarm = 10 ° F
An alarm is initiated above 310 °F or below 290 °F. If the setpoint is changed to 350°F, the
alarm will be initiated above 360 °F or below 340 °F. The setting always represents an amount
above and below the current setpoint.
To change the alarm setting for a zone:
1. Touch the zone to be changed.
2. Touch the Alarm Window field and enter a new value.
3. Touch the Accept button.