v 2.3 — September 2015 Altanium Delta3
134 Mold Cooling Enable
10.1.17 Mold Cooling Enable
The Mold Cooling Enable Limit defines the threshold the system uses to determine when to
activate or deactivate the Mold Cooling Enable output.
Digital output 5 is activated when this output's In Use checkbox is selected and all automatic
zones have exceeded the Mold Cooling Enable Limit. This output is de-activated once the
system is in the 'Stop' state and all automatic zones have cooled down past the same limit.
To set the Mold Cooling Enable value, do the following:
1. On the System Setup screen, under Mold Cooling Enable, touch the Mold Cooling
Enable field.
2. Enter the desired value.
3. Touch the Accept button.
No Response Limit This is a global setting that determines how long
the system should apply 96% power or greater
without a 5 degree rise in temperature before it
is declared an alarm condition. The default value
is 4 minutes and the valid range is 2 to 15
minutes.
At Temperature Minimum Limit This value defines the minimum threshold for
activating the At-Temperature signal. The At-
Temperature signal is activated based on
following:
When all active zone temperatures are higher
than the lower alarm limit.
If the alarm band setting is lower than the At-
Temperature Minimum Limit value, then the At-
Temperature Minimum Limit value is used to
activate the At-Temperature signal.
Table 10-7 Zone Alarm Control Settings (Continued)
Setting Description