12: Scripts
EMG™ Edge Management Gateway User Guide 269
# Wait for the first prompt
set loggedIn false
while {! $loggedIn} {
expect {
timeout {myprint "Timeout waiting to login"; abortSession 3}
"*CDU: " {set loggedIn true}
} ;
}
# Detect the prompt
exp_send "\n"
expect "are:\r\n"
expect "LOGIN\r\n"
expect "REMOVE\r\n"
expect "RESTART\r\n"
expect {
timeout {myprint "Timeout waiting for prompt"; abortSession 3}
-re "\r\n(\[^\r]*:)"
}
set pduPrompt $expect_out(1,string)
# Run the ostat command
exp_send "ostat .b1\n"
expect "Outlet*Power\r\n"
expect "ID*Watts*\r\n"
expect {
timeout {myprint "Timeout waiting for load"; abortSession 3}
-re "\.B1\\s+\\S+\\s+\\S+\\s+(\\S+)"
}
set pduLoad $expect_out(1,string)
myprint "Outlet B1 Load: $pduLoad Amps"
expect $pduPrompt
exp_send "logout\n"
wait -i $sessionId
exit 0