9 Diagnostics & error management
9.9 Error messages of the operating system
658
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oH3: Motor temperature (X106) triggered [xx.0119.00015]
oC5: Ixt overload [xx.0119.00050]
ot1: Maximum torque reached [xx.0123.00001]
oC7: Motor overcurrent [xx.0123.00007]
Response (Lenze setting printed in bold) Setting: C00585 ( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
The motor is overheated so that the thermal contact
integrated into the motor has been switched.
An open circuit or a loose contact at the connections
mentioned above has occurred.
Check motor temperature monitoring.
Provide for sufficient cooling of the motor.
Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold) Setting: C00604 ( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The Ixt overload check has tripped.
Operating threshold = 100 % Ixt (adjustable in
C00123
)
Possible causes:
Wrong dimensioning of the device with regard to its
motor load.
Load cycles are not complied with.
Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
Reduce motor load cycles (observe load cycles
according to documentation).
Response (Lenze setting printed in bold) Setting: C00608 ( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device indicates that the maximally possible torque
at the motor shaft has been reached.
C00057
displays the current torque.
Reduce motor load.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Maximum current monitoring has tripped.
The instantaneous value of the motor current has
exceeded the limit value set in C00939
.
Check and, if required, correct dimensioning of the load
with regard to the installed device power.