oH3: Motor temperature (X106) triggered [xx.0119.00015]
oC5: Ixt overload [xx.0119.00050]
ot1: Maximum torque reached [xx.0123.00001]
oC7: Motor overcurrent [xx.0123.00007]
Response (Lenze setting printed in bold) Setting: C00585 ( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
• The motor is overheated so that the thermal contact
integrated into the motor has been switched.
• An open circuit or a loose contact at the connections
mentioned above has occurred.
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold) Setting: C00604 ( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The Ixt overload check has tripped.
• Operating threshold = 100 % Ixt (adjustable in
C00123
)
Possible causes:
• Wrong dimensioning of the device with regard to its
motor load.
• Load cycles are not complied with.
• Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
• Reduce motor load cycles (observe load cycles
according to documentation).
Response (Lenze setting printed in bold) Setting: C00608 ( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device indicates that the maximally possible torque
at the motor shaft has been reached.
• C00057
displays the current torque.
Reduce motor load.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Maximum current monitoring has tripped.
• The instantaneous value of the motor current has
exceeded the limit value set in C00939
.
Check and, if required, correct dimensioning of the load