- 9 -
Earthquake
protection
When the earthquake detection device acts and
inputs a signal to the system, the elevator lands at the
nearest oor and stops running. After the earthquake
signal becomes inactive and the fault is reset manually,
the elevator restores to normal running.
-
Independent
working power
supply
The NICE1000new system supports not only three-
phase 380 VAC but also single-phase 220 VAC to
meet different applications of the power supply system
(such as 220 V UPS)
-
Automatic voltage
identication
The system detects the bus voltage and automatically
adjusts the running speed of the elevator to adapt to
the situation of insufcient power from power supply
(such as emergency UPS).
-
Parallel Control and Other Functions
Parallel control The system supports parallel control of two elevators. Refer to 5.2.2
Dispersed waiting
In parallel control, the elevators can wait at different
oors.
Set in Fd-05
Parallel control exit
If the parallel control exit switch of a certain elevator in
a parallel control system is valid or the time for exiting
the parallel control is reached, the elevator exits
parallel control and runs independently. This does not
affect normal running of the parallel control system.
-
Parallel control
automatic exit
If an elevator in the parallel control system cannot
respond to calls in time due to faults, the elevator
automatically exits the parallel control system and runs
independently. This does not affect normal running of
the parallel control system.
-
Anti-nuisance
function
The system automatically judges the number of
passengers in the car and compares it with the number
of registered car calls. If there are excessive car calls,
the system determines that it is nuisance and cancels
all car calls. In this case, passengers need to register
correct car calls again.
F8-13 (Anti-
nuisance function)
Prompt of non-door
zone stop
The system gives a prompt when the elevator stops at
a non-door zone area due to faults.
-
Interface for
intelligent
residential
management
The system provides an interface for intelligent
residential management to perform remote monitoring
on the state of elevators in the residential district.
Residential
monitoring board
MCTC-MIB
required
Parameter copy
You can upload and download parameters by using
the operation panel MDKE6.
MDKE6 operation
panel required
Energy-Saving Functions
Car energy-saving
If there is no running command within the set time, the
system automatically cuts off the power supply to the
lamp and fan in the car.
F9-01 (Time for
fan and lamp to
be turned off)