6-60
6-8 List of Modbus Communication (Modbus-RTU) Data
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
6
Communication Function
144Eh
Communication Parity
Selection
C074 R/W
00: Disabled
01: Even
02: Odd
144Fh
Communication Stop Bit
Selection
C075 R/W
1: 1 bit
2: 2 bits
1450h
Operation Selection on
Communication Error
C076 R/W
00: Trip
01: Trip after deceleration
stop
02: Ignore
03: Free-run stop
04: Deceleration stop
1451h
Communication Error
Timeout Time
C077 R/W
0: Timeout disabled
0.01 [s]
1 to 9999
1452h
Communication Wait
Time
C078 R/W 0 to 1000 1 [ms]
1453h
to
1454h
Reserved −−
1455h FV Adjustment C081 R/W 0 to 2000 0.1 [%]
5-40
1456h FI Adjustment C082 R/W 0 to 2000 0.1 [%]
1457h
to
1458h
Reserved −−
1459h Thermistor Adjustment C085 R/W 0 to 2000 0.1 [%] 5-120
145Ah
to
145Eh
Reserved −−
145Fh Debug Mode Selection C091 R
For factory adjustment (Do
not change.)
−−
1460h
to
1463h
Reserved −−
1464h
Communication
Selection
C096 R/W
00: Modbus communication
(Modbus-RTU)
01: Co-inverter
communication
02: Co-inverter
communication
(management)
6-22
1465h Reserved −−
1466h
Co-inverter
Communication Starting
Station Number
C098 R/W 1 to 8
6-221467h
Co-inverter
Communication Ending
Station Number
C099 R/W 1 to 8
1468h
Co-inverter
Communication Starting
Selection
C100 R/W
00: 485 terminal
01: Always started
1469h
UP/DWN Storage
Selection
C
101 R/W
00: Do not store frequency
data
01: Store frequency data
5-71
Register
No.
Function name
Parameter
No.
R/W
Monitor and setting
parameters
Data
resolution
Page