EasyManua.ls Logo

Omron SYSDRIVE MX2 SERIES - Page 52

Omron SYSDRIVE MX2 SERIES
446 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-25
2-2 Wiring
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
2
Design
2. For Source Logic
P24
PSC
SC
S1
Shorting line
P24
PSC
SC
S1
Switch OFF
Without this diode, a sneak current path is generated
and the input turns ON when the switch is OFF.
Power ON
Power OFF
Shorting
line
Input ON
Add a diode
P24
PSC
SC
S1
P24
PSC
SC
S1
Switch OFF
Install a diode instead of the shorting
bar to prevent the sneak current path.
Power ON
Power OFF
Input OFF