4-10
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
4
Parameter List
PID control
A071 PID Selection
00: Disabled
01: Enabled
02: Reverse outupt enabled
00 no yes −
5-73
A072 PID P Gain 0.00 to 25.00 1.00 yes yes −
A073 PID I Gain
0.0 to 999.9
1000. to 3600.
1.0 yes yes s
A074 PID D Gain
0.00 to 99.99
100.0
0.00 yes yes s
A075 PID Scale 0.01 to 99.99 1.00 no yes
Time
A076
PID Feedback
Selection
00: FI (current)
01: FV (voltage)
02: Modbus communication
(Modbus-RTU)
03: Pulse train frequency
10: Operation function output
00 no yes −
A077
PID Deviation
Reverse Output
00: Disabled
01: Enabled
00 no yes −
A078
PID Variable
Range Limit
0.0 to 100.0 0.0 no yes %
A079
PID
Feedforward
Selection
00: Disabled
01: FV (voltage)
02: FI (current)
00 no yes −
AVR
A081
AVR Selection 1
00: Always ON
01: Always OFF
02: OFF during deceleration
02 no no
− 5-27
A281
AVR Selection 2
02 no no
A082
Motor Incoming
Voltage
Selection 1
200V class: 200/215/220/230/
240
400V class: 380/400/415/440/
460/480
200/
400
no no V
5-26
5-148
A282
Motor Incoming
Voltage
Selection 2
200/
400
no no V
A083
AVR Filter Time
Parameter
0.000 to 10.00 0.300 no yes s
5-27
A084
AVR
Deceleration
Voltage Gain
50. to 200. 100. no yes %
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page